Monday, April 13, 2009

NEBS vs. the Hottest Place on Earth

As mentioned in Higher Temperatures for Data Center and Processors for Higher Temps, various groups are pushing for higher and higher ambient temperatures in data centers. At Google's Efficient Data Center Summit last week, Amazon's James Hamilton brought up an interesting point in his slides and blog about ambient temperatures:
the hottest place on earth over recorded history was Al Aziziyah Libya in 1922 where 136F (58C) was indicated

James went on to note during his talk that telecommunications equipment designed to the NEBS (Network Equipment Building System) standards routinely has to handle temperatures up to 40°C.

Actually, the story is better than that. NEBS-GR-63 (the key NEBS specification dealing with environmental conditions for equipment in telecommunications central offices) requires equipment to handle 40°C long-term ambient temperatures, but telecommunications equipment certified at the shelf (chassis) level needs to be able to operate at 55°C ambient for up to 96 hours at a time and up to 360 hours per year [the 360 hours is for reliability calculations]. This means that much of the NEBS-rated equipment for data centers can operate at temperatures that are only 3°C lower than the highest natural temperature ever recorded on Earth, as noted by James.

Given the common engineering penchant to provide some guardband on products vs. the official specifications, even a 58°C ambient is not out of the question. This means that NEBS-rated equipment could be good candidates for data centers operating at high temperatures.

But can you get decent performance in NEBS-rated servers? Yes! For example, vendors such as Radisys, Kontron, and Emerson have announced blade servers with Intel's new 5500 (aka "Nehalem") processors, and their bladed servers commonly are NEBS certified to operate at 55°C. This would allow the latest server technology to operate in the most demanding environments.

--kb

Friday, February 13, 2009

Processors for Higher Temps

Higher Temperatures for Data Centers talks about emerging environmental standards that could well lead to increasing ambient temperatures in facilities. All other things being equal, higher ambient temperatures will lead to higher component temperatures.

In many cases, the maximum processor case temperature (Tcase) is the limiting factor for how high the ambient temperature can be raised. The Tcase limit is established by the semiconductor vendor as the maximum case temperature that the chip can experience and still meet the vendor's reliability goals.

This can put a crimp in plans to use outside air for cooling. In most likely data center locations, there are occasionally warm days that would increase the inlet temperature to the servers to the point that the processor Tcase would exceed the vendor's specified ratings.

The telecommunications market has had this issue for years.
NEBS-rated equipment for central offices generally has to operate at 40°C ambient temperature, but they also need to operate at 55°C for short periods (up to 96 hours at a time and up to 360 hours per year).

To address the needs of the NEBS market, Intel provides some of their processors with
dual Tcase ratings: one long-term T-case rating and a second short-term Tcase rating that is 15°C higher for up to 360 hours per year.

These processors with dual Tcase ratings may be a good fit for systems in data centers that use air-side economizers.

Tuesday, February 3, 2009

Using Outside Air for Data Centers

Conventional wisdom holds that it takes one Watt of cooling to remove every Watt of ICT equipment inside the data center. Today's data centers can do a bit better than that, but cooling costs remain a considerable OpEx cost for facilities.

One approach that's generating increased interest is the use of dry-side economizers, which bring in outside air to cool the data center. Using outside air saves the power that is normally used by compressors and chiller plants to cool facilities; even bigger gains may be achieved by avoiding CapEx (Capital Expense) costs by eliminating the purchase of chiller plants entirely or at least reducing CapEx costs by installing smaller cooling plants.

At first blush, this approach may seem to only be of marginal value. However, higher density data centers (such as those with blade servers) may have a relatively large temperature increase between inlet and exhaust temperature. Even if the desired inlet temperature is only 75°F, a facility with a 50°F temperature rise would have an exhaust temperature of 125°F--most ambient temperatures are well below this temperature. Bringing in outside air could take less energy than cooling the recycled air--humidity considerations notwithstanding.

To look at the impact of using outside air to cool data center equipment, several data center operators have performed small-scale tests to see how data center equipment is impacted by outside air:

Air economizers look promising, based on these results.

--kb